![]() |
![]() |
![]() |
![]() |
Click to view schematic display A | Click to view schematic display B | Click to view schematic display C | Click to view schematic display D |
![]() |
|||
Click to view schematic display E | |||
Simtronics’ Steam Turbine with Generator program represents a typical
steam turbine used for electric power generation. The scope of the
program includes the condenser, the vacuum system and the hotwell. The
steam turbine drives an electric generator connected to a large,
regional electric power grid. Simtronics’ Steam Turbine with Generator
simulator requires the operator to manually synchronize the gas
turbine/generator set with the electric grid before connecting to it.
This allows the operator to understand the concept of synchronization
and its importance in keeping the generator from being damaged during
connection to the electric power grid, since most real industrial
systems use an auto-synching device/system to connect a generator to a
power grid.
A full range of operations can be learned and practiced on the Steam
Turbine with Generator simulator. These include normal, startup,
shutdown, and emergency shutdown procedures.
Steam Turbine with Generator
The Steam Turbine with Generator program represents a typical
gas turbine/power generator unit found in a power plant. High pressure
steam generated in the power plant is used to drive the Steam Turbine
which turns an electric power generator. The exhaust from the steam
turbine is condensed with cooling water and is returned to the boiler
feed water preparation section of the power plant. Electric power
produced by the generator is delivered to a power grid for distribution
to electric power users.
Superheated high pressure (HP) steam from battery limits enters the
Steam Turbine JT-301 under control of the turbine control system which
regulates the inlet throttle valve SV-301. JT-301 is a three-stage
turbine; the first stage exhausts intermediate pressure (IP) steam which
is routed to IP Desuperheater J-301 prior to passing through the IP
Reheating Coils E-303 of an HRSG. Increasing the temperature of the IP
steam before using it in the second stage increases the power
availability of the steam and makes the power generation cycle more
efficient. Reheated IP steam from E-303 is readmitted to JT-301 and
passes through the IP stage of the steam turbine and then to the low
pressure (LP) stage within the same casing. Steam exiting the LP stage
is exhausted directly to the shell side of Surface Condenser E-301 which
uses cooling water to condense the exhausted steam from JT-301.
E-301 normally condenses all the steam from JT-301. The condensate from
E-301 drains directly into the Hotwell D-301. The pressure of E-301 is
essentially determined by the vapor pressure of the condensate leaving
E-301 so it normally operates at vacuum conditions. To ensure vacuum
conditions are maintained, the Vacuum Ejector EJ-302 pulls a small flow
of low pressure vapor from E-301 using medium pressure steam from
battery limits as the motive fluid. The motive steam and vapor from
EJ-302 are condensed in Vacuum Condenser E-302 using cooling water. The
condensate from E-302 drains into the Hotwell D-301.
At startup or in case of leaks of air into E-301 or in case of
non-condensables in the HP steam, the pressure in E-301 may build due to
pocketing of the non-condensable vapor. If this occurs, the Startup
Ejector EJ-301 can be placed in service to exhaust the vapor directly to
atmosphere via a vent.
The Hotwell D-301 is a vertical drum directly connected to outlet of
Surface Condenser E-301 and collects steam condensate from E-301 and
E-302. The condensate is pumped by Condensate Return Pumps P-301A/B to
the Deaerator in the BFW treatment section at battery limits for reuse
as boiler feed water. Either pump can be set to auto-start in case of
high level in D-301.
Steam Turbine Controls and Instruments
The HP steam flow to JT-301 is indicated on FI-301. The supply pressure
of HP steam is indicated on PI-301 and its temperature is indicated on
TI-301. HP steam passes through trip valve XV-301 which is controlled by
HIC-301. HP steam flow can also pass through a smaller warm-up line at
startup. HIC-302 controls the warm-up valve HV-302 on this line. Speed
controller SIC-301 regulates the opening of speed control valve SV-301
inside the turbine casing. SV-301 controls the flow of HP steam to the
first stage of JT-301.
The speed of the shaft of JT-301 is measured by SI-301. This instrument
is also used by the speed control system for JT-301. The speed of
JT-301, expressed as % of design speed (3,600 RPM), is indicated on
SIC-301. SIC-301 normally operates in cascade mode when Generator G-301
is connected to the electric power grid. This control mode is entered by
placing droop control switch HS-303 into the DROOP state. Droop control
is explained in the next section. SIC-301 can be taken out of
droop/cascade control and placed in automatic or manual mode. Automatic
mode is used only at startup when the generator is not connected to the
grid. In this case, SIC-301 directly controls the shaft speed. In manual
mode, SIC-301 is used to manually adjust the HP steam flow to JT-301.
Manual mode of SIC-301 is available any time the Steam Turbine is not
tripped. Manual mode is entered any time the droop control switch HS-303
is changed from the DROOP to the OFF state.
The pressure of IP steam exhaust from JT-301 is indicated on PI-302 and
its temperature is indicated on TI-302. The IP steam is reheated in
E-303 using HRSG flue gas. The flow of flue gas to E-303 is controlled
by HIC-311. The outlet temperature of reheated steam is controlled by
TIC-303 which controls the rate of injection of HP boiler feedwater
through TV-303 to the IP steam line upstream of E-303. The outlet
pressure of steam from E-303 is indicated and controlled by PIC-303. An
IP steam admission valve PV-303 is provided on JT-301. Normally this
valve is wide open at design operation. However, PIC-303 will regulate
this valve to make sure the IP steam does not drop below 300 PSIG at the
outlet of E-303. Too low an IP pressure can lead to condensate in the
exhaust from the 1st stage turbine of JT-301 which will quickly erode
the turbine blades.
The pressure of cooling water to Surface Condenser E-301 is indicated on
PI-305 and its temperature is indicated on TI-305. The flow of cooling
water to E-301 is controlled by HIC-305 which adjusts the valve opening
of HV-305. The temperature of steam condensate leaving E-301 is
indicated on TI-304 and its pressure is indicated on PI-304. The
temperature of cooling water leaving E-301 is indicated on TI-306.
The shaft speed of Generator G-301 is indicated on SI-302. The power
output of G-301 is indicated on JI-320.
Generator G-301 is provided with a synchroscope in order to visually see
the difference of the frequency and phase between electricity produced
by G-301 and the electric grid at startup. Generator G-301 is connected
to the electric power grid using switch HS-322. SI-320 indicates the
frequency of electricity at the terminals of G-301. SI-321 indicates the
frequency of electricity of the electric grid after the breaker switch.
SI-322 indicates the phase difference between electricity generated at
the terminals of G-301 and the electric grid. Before connecting the
Generator to the grid with breaker switch HS-322, the frequencies of the
Generator must be the same and the phase difference must be nearly zero.
Otherwise, the Generator may suffer major damage when the breaker switch
is closed.
Droop Control
When any synchronous electric generator is connected to a large grid in
parallel with many other synchronous machines such as generators and
electric motors, a single generator cannot easily or reliably control
the frequency of the electric power of the grid because it is only
generating a small fraction of the total power being consumed from the
grid. In this case, the generator will run at the grid speed or
frequency. Therefore, the speed of the power turbine that drives the
generator cannot be controlled when the generator is connected to a
large grid.
The grid frequency dynamically depends directly on the balance of power
generation and consumption across the grid. If generators are producing
more power than the power consumers on the grid, the grid frequency will
increase, causing all synchronous motors connected to the grid to speed
up. As they speed up, they will consume more power until the power
consumption comes into balance with power generation. In order for many
generators to supply electricity to a large grid, they cooperatively
adjust their power output using what is known as droop control.
Droop control simply proportions a generator’s power output to the
deviation between of the actual grid frequency and its setpoint
frequency (60 Hz). If the actual grid frequency is at the setpoint, the
generator will put out its design power. When the grid frequency is
higher than the setpoint, the generator will decrease its power output
in proportion to the deviation. Each generator system with droop control
is configured with a characteristic droop control constant, expressed as
% of setpoint speed. For JT-301/G-301 this constant is 4%. At 4%
overspeed of the grid (i.e. 62.452 Hz) the droop controller will adjust
the power output to the minimum stable power operation for JT-301/G-301.
When SIC-301 is placed into droop mode using switch HS-303, the PV of
SIC-301 is computed as follows:
PV = [SI-321.PV * 60 + (SIC-301.OP - 13.0) * 2.542373] * 100/3,600
The setpoint of SIC-301 is locked at 104.0 when in droop mode. Any
deviation of the grid frequency (SI-321.PV) will cause SIC-301 to move
its output such that the PV is restored back to the setpoint of 104.0.
The integral action of controller SIC-301 will cause the output (and
power) to move gradually.
Vacuum System Controls and Instruments
The flow of medium pressure (MP) steam to the vacuum system is indicated
on FI-307. The pressure of MP steam is indicated on PI-307.
The flow of steam to Startup Ejector EJ-301 is controlled by HIC-306
which adjusts the opening of valve HV-306. The flow of steam to Startup
Ejector EJ-301 is controlled by HIC-306 which adjusts the opening of
valve HV-306.
The flow of cooling water to Ejector Condenser E-302 is controlled by
HIC-308 which adjusts the valve opening of HV-308.
Hotwell Controls and Instruments
The level of condensate in Hotwell D-301 is indicated and
controlled by LIC-301 which adjusts the position of LV-301 on the
discharge of the Condensate Return Pumps P-301A/B. The flow of
condensate taken to the Deaerator is indicated on FI-309.
The motors of Condensate Return Pumps P-301A/B are operated by switches
HS-301A and HS-301B, respectively. LAH-301 also indicates the level of
condensate in D-301 and its high alarm signal (80% setpoint) is used to
auto-start P-301A or P-301B by selecting the AUTO state of switch
HS-302A for P-301A or by selecting the AUTO state of HS-302B for P-301B.
Normally one pump is in service with its auto-start switch in the MAN
state and the other pump is on standby with its auto-start switch in the
AUTO position.
Interlock I-301
Interlock I-301 protects the Steam Turbine from overspeed and
mechanical problems. I-301 activates on any of the following inputs:
HS-301 serves as both a trip and reset switch. All other trip inputs
must be cleared in order to reset I-301.
When I-301 trips, the following actions occur:
Interlock I-302
Interlock I-302 protects the Generator from damage when disconnected
from the grid and from mechanical problems. I-302 activates on any
of the following inputs:
HS-322’s signal is a one-shot signal to allow a reset of I-302 when
restarting. HS-302 serves as both a trip and reset switch. Trip
input XA-321 must be cleared in order to reset I-302.
When I-302 trips, the following actions occur: